1Motor
2Starter
3Overload
4Factory forms — optional
✓Selection
5Account manager
NotesOptional. Added to the email, copied list and parts list file. Not saved on this device.
Reference tables
Type S starter ratings NEMA Sizes 00–6
Digest 179 Tables 16.86, 16.89 and 16.163. Size 1P is single-phase only. Size 7 is offered in the TeSys N line.
Catalog types by enclosure 8536 three-phase, single-phase, 8736 reversing
Full catalog number = class + type + coil code + forms in alphanumerical order, for example 8536SCG3V02H30S. For melting alloy heaters, leave out the H30 form. "—" = not offered.
Motor Logic SSOLR dial ranges Forms H30, H300, H301, H308, H309
Digest Table 16.315 (special factory-assembled combinations) and Table 16.275. Class 10/20 selectable, phase loss and unbalance protection.
Coil voltage codes
All Type S coils are AC. 24 VAC coils aren't available on Sizes 4–6; on Sizes 00–3 they need Form S. For a 24 VDC control signal, use an interposing relay. Form S (separate control) is needed whenever the coil isn't fed from the motor line.
NEC motor full-load current Tables 430.248 & 430.250
Use the table current to size the starter and conductors (NEC 430.6(A)(1)). Set overloads from the motor nameplate FLA (NEC 430.6(A)(2)).